Do the GV3 starters have de-rating based on ambient temperatures?

 Issue:
Customer wants to use the GV3 starter in ambient temperature of 50C.  Asking for de-rating information.

Product line:
Tesys GV

Environment:
all

Cause:
Catalog does not show temperature de-rating info.

Resolution:
The GV3P can operate from -20 to +60C in open spaces or -20 to +40C in enclosures without derating because they have a temperature compensation system. 

The temperature limitation for enclosures is due to air circulation around the product being limited.  No derating is available above or below this temperature range.

 