How do you wire a 8903LO electrically held lighting contactor to a photocell control?

 Most standard photocells have 3 wires.   Black is supply voltage, L1, white is neutral or L2, and red is the switched leg.   You run the switched leg to one side of the coil and the other side of the coil to the neutral or L2.   See attached diagram.