What are the recommendations for connecting PTC to the Altistart ATS48?

Issue:
What are the recommendations for connecting PTC to the Altistart ATS48?

Product Line:
ATV
 
Environment:
All

 
Cause:
Wiring

 
Resolution:
Manual shows the following;
PTC1, PTC2 -  Total resistance of probe circuit: 750 Ω at 25 °C/77 °F
• For example, three 250 Ω probes in series