Technical FAQs

Ask a Question

Do LVCTs (Low Voltage Current Transformers) need shorting blocks?

Issue 
User needs to know if LVCTs can be installed on their own or if they need shorting blocks. 

Product Line 
LVCTs, Rogowski Coils 

Environment 
Installation of meter using LVCTs. 

Cause 
User is unsure if shorting blocks are necessary to use when installing LVCTs. 

Resolution 
LVCTs do not need shorting blocks. If a 0.33V CT is shorted, the internal burden resistor and the CT would be shorted at the same time.
This would effectively be the same as shorting a current secondary CT. While this would cause no harm, it is unnecessary. 
Was this helpful?
What can we do to improve the information ?