What is the maximum power consumption rating of the 24V supply for ATV630 drive?

Issue:
What is the maximum power consumption rating of the 24V supply for ATV630 drive?

Product Line:
Altivar 630

Environment:
All

Cause:
Power consumption

Resolution:
  • +24 Vdc
  • Tolerance: minimum 20.4 Vdc, maximum 27 Vdc
  • Current: maximum 200 mA for both 24 Vdc terminals
  • Terminal protected against overload and short-circuit
  • In Sink Ext position, this supply is powered by external PLC supply