Can the Altivar ATV340 programming be saved to the VW3A1111 Keypad?

Issue:
Can the  Altivar ATV340 parameters be saved to the VW3A1111 Keypad?

Product Line:
Altivar 340
 
Environment:
All
 
Cause:
Configuration
 
Resolution:
The ATV340 works the same way as the ATV630 and ATV930.  Browse to [Main Menu] > [File Management] > [Transfer Config File] > select "Copy from the drive" to backup to the keypad.