Can a transformer with the voltage code T64H, regardless of the KVA rating, be wired to get 480V delta on the secondary output?

Issue:
Can transformers with a delta wye secondary output be wired for a delta configuration?

Product Line:
transformer

Environment:
Low voltage dry type transformer

Resolution:
Yes, they just leave the H0 alone and not hook anything up to it.