How do you set up the ATS48 soft starter to read KWs in the SUP menu?

Issue:
How do you set up the ATS48 soft starter to read KWs in the SUP menu?

Product Line:
ATS48

Environment:
All 

Cause:
Wants to read the KW settings in the SUP menu 

Resolution:
Make sure the ATS48 is stopped.  Arrow down to the DRc menu hit enter  find ULn enter set to 480vac or what ever your line voltage is to calculate the correct KW settings. 