What is the part number for a transformer rated 250VA, 277 - 120V with fusing?

Issue:
What is the part number for a fusible control power transformer (CPT) rated 250VA, with  277V primary - 120V secondary?

Product Line:
control power transformer

Environment:
Class 9070TF

Resolution:
For a 250VA transformer rated 277V - 120V with fusing we suggest the 9070TF250D4. The primary fuse size is 2 - 2.5A and the secondary is 3A. The transformer accepts class cc fuses. 

 