Can the B-frame breakers be used on delta systems?

Issue:
Are there any B-frame circuit breakers that are rated for delta voltage systems?

Product Line:
Powerpact Molded Case Circuit Breakers

Environment:
Powerpact B-Frame Circuit Breakers

Resolution:

The 600Y/347 V rated B-frame circuit breakers (ie. BGL36100) are rated for use on 240 Vac and 480 Vac delta voltage systems. None of the B-frames are rated for use on 600 Vac delta voltage systems.