What is the basic programming for an ATV630 replacing an ATV66 in a Trane Unit?

Issue:
What is the basic programming for an ATV630 replacing an ATV66 in a Trane Unit?

Product Line:
ATV630

Environment:
All

Cause:
Programming

Resolution:
On ATV66 wires on LI1 Run Perm., LI2 Run Fwd, so swap wire LI2 goes to DI1 for RF, LI1 to DI2 as nSt. 
Command and Ref > Reverse Assign to NO
Freewheel Stop to DI2
On AI2 you had a temp sensor that looks like a resistor, not used on ATV630.
ATV66: LI3 was switch frim Hand to Auto,  ATV630: 5.5 menu: Set DI3 to Ref 1B switching
ATV66: LI4- Fault reset  ATV630- 5.12 menu: Fault reset - DI4
Ref Freq. 1 Config  is set to AI1


 