When will XW/SW or MPPT End absorption charging?

Issue:
When will my battery bank end Absorption charging?

Product Line:
Conext XW+/SW & MPPT

Environment:
Charging with Conext inverters and charge controllers

Cause:
N/A

Resolution:
The system will finish the absorption charging stage when the charging amps drop to 2% or below of selected Battery Capacity OR when the absorption time is met. If you want to exit absorption based on time ONLY see article FA309666.