Program Viewer web page for the BMENOC0311 returns the error 'Couldn't dynamic plc content'.

Goals and Symptoms
The Program Viewer web page for the BMENOC0311 Factorycast module returns the error 'Couldn't dynamic plc content'.

Facts and Change
BMENOC0311

Causes and Fixes
The Program Viewer web page for a BMENOC0311 Factorycast module returns the error 'Couldn't dynamic load plc content.






This will occur if the Unity application project settings is not configured for the  Program Viewer.

To resolve the issue:
  • Open the Project Settings for the Unity application.
  • Click on 'PLC Diagnostics'
  • Select the checkbox labeled 'Program Viewer Information'
  • Click on 'Apply'.
  • Click on 'OK'.