Is it possible to use different voltages on the field side of an Telefast ABE- 7P16F310?

Issue:
Does the Telefast ABE-7P16F310 allows for different voltages to be used on the field side of the module?

Product Line:
Telefast, Modicon, Telemecanique

Environment:
PLC, Interfacing relay

Resolution:
Yes you can use different voltages on the field side of the module. The voltage to be used will be determined by the solid state plug in module used. Here is a list of the available modules:

ABS-7EC3AL (5 VDC TTL)
ABS-7EC3B2 (24 VDC)
ABS-7EC3E2 (48 VDC)

ABS-7EA3E5 (48 VAC)
ABS-7EA3F5 (110/130 VAC)
ABS-7EA3M5 (230/240 VAC)