What is the smallest AC wire size I can use for XW+/CSW inverters?

Issue:
What is the smallest AC wire size I can use for XW+/CSW inverters?

Product Line:
Conext XW+/SW

Environment:
Conext inverter Installation and design

Cause:
Not applicable.

Resolution:
Minimum AC wire size for XW+ units it is #4 AWG and for the SW units it is #8 AWG.