How do you find the IP address for an IFE?

Issue:
What is the IP address for a circuit breaker connected to an IFE module?

Product Line:
Circuit Breakers

Environment:
Masterpact and Powerpact Micrologic

Resolution:
The breaker doesn't have an IP address.  The IP address belongs to the IFE module. By default, the first two sets are always 169.254. The next two sets are on a label on the IFE written in HEX format, which must be converted to decimal. As an example, if a label on an IFE is "IFE-E3.AB.7C", AB converts to 171, 7C converts to 124, and the complete IP address is 169.254.171.124.