How do you configure a relay output on ATV630/930 to indicate safety input status?

Issue:
On the Altivar Process 630/930, we need a relay to indicate if safety input is active or not

Product Line:
Variable Frequency Drives

Environment:
Applies to Altivar Process 630 and 930

Cause:
We need to have an indication when the safety circuits on the drive STOA or STOB are open

Resolution:
You can configure one of the relays of the drive to "Power Removal State"

Go to Complete Settings
Go to Input/Output Relay
Go to Rx Configuration
Set Rx assignment to "Power Removal State"

Replace x with the number of the relay you want to use.

 