Can the ATS01 be used at 400V?

 Issue:
Customer wants to use the unit with 480V supply for a 415V rated motor.

Product line:
ATS01, Altistart 01

Environment:
n/a

Cause:
n/a

Resolution:
The ATS01 is a softstart, that onces it reaches full speed/output will provide the full line voltage to the motor.  The ATS01 are rated up to 460VAC, so can be used with a 400V or 415V rated motor. 

If they need to supply 480V for a 415V rated motor, they will have to change the voltage from 480V to 415V. 
 