Can an ELM module be used on a 208 or a 120 V system?

Issue:
What is the minimum voltage system an ELM module can be applied on?

Product Line:
Circuit Breakers

Environment:
ELM module

Resolution:
The ELM150HD and ELM250JD may be applied on systems only between 240 and 600 Vac.  The electronics are powered from bus voltage and the voltage must be in this range.