Does the OSP sticker need to be ordered separately for SIP,SID,SIX medical panels? This is required by OSHPOD.

Issue:
Doe the medical panels like the SIP,SID,SIX come with the OSP sticker required by OSHPOD?

Product Line:
Medical Isolation panel

Environment:
SID,SIP,SIX

Resolution:
No. The OSP / Sesimic sticker is only included and available on Hospital or Medical Isolation Panels that have the NQ bolt on interior. This would exclude all Controlled panels and any panel with QO loadcenters that accept only plug on breakers. If they have any of these two panels and require the label, they will have to replace the panel with one with the NQ bolt on interior. Replacement labels are not available.