How are 800A and above, PTQ style busway plug in units bolted to current style busway?

Issue:
How do you connect 800A, 1000A, or 1200A  PTQ type busway units to I-line II busway?

Product Line:
Busway

Environment:
AP and CP I-line II busway

Resolution:
The 800A and larger fusible plug-in units have catalog numbers beginning  with "PTQ" and utilize a bolted connection to the busway, requiring the removal of the plug-in base on the busway to make the connection. Once the plug in base adapter is removed they can bolt the switch unit to the busway.