How to connect 4203DR current sinking AOUT to PLC with current sinking AIN?

AOUT on 4203 cannot be connected directly to AIN on the SP350 because both are current sinking type of I/O.
Drawing shown below describes how AOUT on 4203DR transmitter should be connected to AIN on SCADAPack 350 when I-I Isolator is used.
Jumper for analog input on SCADAPack 350 must be in the Current position.