How to perform a factory reset on the ATV630 drive?

Issue:
How to perform a factory reset on the ATV630 drive?

Product Line:
Altivar 630

Environment:
All

Cause:
N/A

Resolution:
From main menu, go down to menu 7 file management and enter.
Go down to 7.2 factory settings and enter.
Go down to parameter group list and select the menus you would like to perform a factory reset on or select all if needed.
You will see a check mark indicating that the groups or specifc menus are selected to be factory reset.
Once that is done ESC back to the 7.2 factory settings menu.
Arrow down to go to factory settings and enter to continue. 