Technical FAQs

Ask a Question

What are default values of stator resistance, inductance RSA, LFA, TRA in ATV320 ?

Issue:
What are default values of stator resistance, inductance RSA, LFA, TRA in ATV320 ? 

Product Line:
Altivar 320

Environment:
All

Cause:
NA

Resolution:
There are no default values of RSA, LFA, TRA in the drive. These values depends on motor data that are entered. NPR, ULN, NCR, NSP
As soon as you enter these data, values RSA, LFA, TRA will be changed. These changed values will be considered by motor control algorithm unless autotuning is executed.
Autotuning will overwrite RSA. LFA, TRA.
Was this helpful?
What can we do to improve the information ?