If a Masterpact breaker has a 100A or 250A sensor plug, can that sensor plug be replaced with a higher amp rating sensor plug?

Issue:
What is the maximum amp sensor plug that can be installed in a Masterpact breaker with 100A or 250A sensor plug?

Product Line:
Circuit Breakers

Environment:
Applies to Masterpact NT and NW Circuit Breakers

Resolution:
In a Masterpact breaker with a 100A sensor plug, it is ok to change the sensor plug to 250A, but not higher than 250A.
In a Masterpact breaker with a 250A sensor plug, it is ok to change to sensor plug to 100A, but not higher than 250A.