Is a 42 circuit NQ panelboard built with 225A bussing?

Issue:
Does the 42 circuit NQ panelboard automatically come with 225A bussing, regardless of the main breaker amperage?

Product Line:
NQ panelboards

Environment:
Specification

Cause:
Selection

Resolution:
All NQ panelbaords except 18 circuit have at least 225A bussing including the 42 circuit, regardless of the main breaker amperage.