Can a neutral kit be field installed in an I-line busway plug in unit: PTQ3680GH, 800A?

Issue:
Can a neutral kit be field installed in an I-line busway plug in unit: PTQ3680GH, 800A?

Product Line:
I-Line busway and accessories

Environment:
Neutral requirement

Cause:
Maintenance

Resolution:
The neutrals can not be added to this unit in the field. These 800A fusible plug-in units have been redesigned. The new catalog number would be PTQ46080GH to include the neutral. Reference table 12.23 on page 12-10 of Digest 177. See attached cut sheet for revised changes.

 