Can feed thru lugs be added to the top of the NQ or NF panel on the I-Line combo panel to accept the incoming cables?

Can NQ or NF panels, in the I-line combo panel, have thru feed lugs added for a top feed application?

Product Line:

I-line combo panel

Cables were cut too short and they need to come into the top of the panel.

No. The NF or NQ panel is the sub panel and is fed from the I-line Power Panel or in a duplex application the sub panels can be fed from one of the branch breakers from the I-line Power Panel. The NQ and NF panels were not designed for use with thru feed lugs for any application. However, a subfeed lug kit can be added to the I-line Power Panel if they want to feed another load from the I-line combo panel.