Is the ATV340 tested and approved for use on Single phase input to run 3 phase motors?

Customer wants to know if he can provide single phase input power to an ATV340 and have it run a 3 phase motor.
Product Line:
Altivar 340 - ATV340
Single phase input power
Customer does not have 3 phase power available.
The ATV340 has not been tested or approved for use on single phase power systems.
It requires 3 phase input power.
There are currently no plans to peform this testing.

It is possible to feed the DC Bus of the ATV340 drive so a front end rectifier may be used.   Bonitron ( has provided this type of device for years.