ATS22 S6U does not run when 120VAC is closed to LI1 and LI2.

Issue:
ATS22 S6U does not run when 120VAC is closed to LI1 and LI2.

Product line:
ATS22 soft starters

Environment:
S6U versions, All serial numbers.

Cause:
Incorrect wiring.

Resolution:
On the S6U version, it is necessary to tie Neutral not only to CL2, but also to the COM terminal.

 