Technical FAQs

Ask a Question

How is the ATV630 programmed for a current threshold relay configuration?

Issue:
How is the ATV630 programmed for a current threshold relay configuration?

Product Line:
Altivar process, ATV630

Environment:
All

Cause:
Relay programming.

Resolution:
To program this function go into Complete settings, Input/Output menu, and click on tab for relay on the botom of the display. 
Enter on a relay configuration that will need to be used for current threshold setting.
Go into the R* assignment setting and program it to current thd reached.
To adjust the threshold levels for low and high threshold go into complete settings, genertic function, and then threshold reached.
You will have low treshold and high current threshold settings that can be programmed as needed.
Was this helpful?
What can we do to improve the information ?