Can you run a smaller test motor on a ATV630 and ATV930 drive?

Issue:
Can you run a smaller test motor on a ATV630 and ATV930 drive?

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
Set up drive for test on small power 

Resolution:
You will need to set up the drive to run the smaller test motor. 
Programming:
Main Menu 
Complete settings:
Motor Parameters 
Motor Control Type=  Set to VF 5 Points

In Simply Start menu set up your motor amps and HP to size of the test motor. 

 