How can you copy a old ATS22/ATS48 program from the old drive into a new ATS22/ATS48 soft starter?

Issue:
Is it possible to copy the settings from an old ATS22/ATS48  soft starter to a new one?

Product Line:
Soft Starters

Environment:
Applies to ATS22 and ATS48

Cause:
Replacing an old ATS22/ATS48 with a new one

Resolution:
You can copy the settings from an old ATS22/ATS48 assuming it is still in working condition using the SoMove software to download the settings to your PC then uploading them back to your new ATS22/ATS48

You will need to download SoMove (Free)
https://www.schneider-electric.ca/en/download/document/SoMove_FDT/

The required libraries for the ATS22/ATS48
https://www.schneider-electric.us/en/download/document/Altistart_DTM_Library/

You will need to buy or use the Modbus cable TCSMCNAM3M002P (TCSM cable driver link is below)
https://www.schneider-electric.com/en/download/document/TSXCUSB+and+TCSMCNAM+DRIVER/

After successfully connecting the old ATS22/ATS48
  • Save the project as a PSX file on your computer. 
  • Now Connect to the new ATS22/ATS48 to Somove
  • Open the project you saved earlier and upload it to the new ATS22 or ATS48 soft stater.

If you are having issues connecting to your ATS22/ATS48 check the link below for troubleshooting
https://www.schneider-electric.ca/en/faqs/FA313062/


Note: Both the old and the new soft starters have to be identical otherwise you can not copy the settings from one another without some modifications of some parameters or manually making the changes

 