With ATV600 ATV900 Process AC Drives why does Analog Output not match the Analog Input?

Issue:
ATV630 ATV930 why does Analog Output not match the Analog Input?

Product Line:
ATV630 ATV930 Process Drive

Environment:
All

Cause:
Reference range has not been set correctly

Resolution:
Ensure that Max Frequency is set to the same frequency as High Speed.  If using a Low Speed other than 0.0hz, set Reference Template to Deadband