Cause:
Customer needs to control multiple motors with one drive
Resolution:
Yes, the ATV61 can run multiple motors as long as the following criteria are met:
1. The drive's horsepower rating has to match or exceed the combined horsepower ratings of the connected motors
2. The total combined current draw of the motors cannot exceed the rated current output of the drive
3. There must be individual overload protection on each motor