Why does the S-Flex with bypass not follow deceleration ramp time and freewheel stops instead?

Issue:
Why does the S-Flex with bybass not follow deceleration ramp time and freewheel stops instead?

Product: 
SFD212, S-Flex with Bypass

Environment: 
All

Cause:
Drive will not follow deceleration time. 

Resolution:
SFD212(S-Flex) with bypass will not follow the deceleration time, because when the stop command is given, the  DOC drive output contactor drops out immediately, causing the run permissive to drop out and the motor is no longer connected to the VFD. The motor then coast (freewheel) to a stop. 