How to program an ATV320 drive to send feedback of motor frequency using the analog output?

Issue:
How to program an ATV320 drive to send feedback of motor frequency using the analog output?

Product Line:
Altivar 320

Environment:
All

Cause:
N/A

Resolution:
Go under CONF, FULL, I/O.
AO1 assignment will need to be set motor frequency.
AO1T for type (current or voltage)
AO1 min for min value such as 0mA or 4mA.
AO1 max for 10V or 20 mA.