Technical FAQs

Ask a Question

What would cause the ATV630 drive not to follow the analog speed reference and ramp up to speed?

Issue
What would cause the ATV630 drive not to follow the analog speed reference and ramp up to speed?

Product Line:
ATV630, ATV930, ATV660, ATV960, ATV680

Environment:
All 

Cause:
Missing analog signal for speed control 

Resolution:
  • Check to see if the drive is seeing the analog input signal in the IO map monitoring menu [Complete settings] [Input/Output] [AI/AQ] (Menu 5.11, AI/AQ tab). Also make sure the analog type is assigned correctly per the signal (0-10V or 4-20mA) that you're using. And that the Min and Max values are set properly according to the range that your signal is using.
  • Check to see if there is a preset speed assigned that is overriding the analog signal. [Complete settings] [Generic functions] [Preset speeds]
  • Check to see if there is an auto manual or reference switching assigned. (This parameter can be accessed if [PID Feedback] PIF is not set to [Not Configured] NO.) If so, check the digital input to see if the input is switching for the correct analog input.
  • Make sure the drive's status on the HMI is showing the status as 'Run' (upper left-hand corner of the display).
  • Check to see if the drive's status is 'CLI', which means the motor is pulling excessive amps and the drive is in current limit mode (upper left-hand corner of the display).
Was this helpful?
What can we do to improve the information ?