Can you use the nld energy savings motor control type on the ATV930 drive run a constant torque load like a gain leg?

Issue:
Can you use the nld energy savings motor control type on the ATV930 drive run a constant torque load like a gain leg?

Product Line:
ATV930 in nld motor control type nld

Environment:
All

Cause:
NA

Resolution:
No, nLd control law is not advice for constant load application whatever load. If you operate at nominal operation point with all control law it will be same (no energy saved) because energy requested by application have to be provided.

 