How many auxiliary devices (Control Power Transformer or Voltage Transformer) can be placed in a structure of Square D Arc Resistant MasterClad Switchgear?

Two auxiliary devices (CPT – max 15kVA or VT) can be mounted in full height structure with no breakers.  One auxiliary device (CPT – max 15kVA or VT) can be mounted in a structure above or below a breaker (max 2000A).
 