How to connect braking resistor to ATV340, 11kW drive ?

For ATV340 smaller sizes (size 1 and size 2), there are terminals PB and PBe on CN10 connector for connecting braking resistor
Size 1 and 2 are ATV340 drives up to U75N4 included


On ATV340 size 3 and bigger, braking resistor must be connected to PA/+ and PB. See attached pict.
Size 3 and bigger = ATV340D11N4 and above