Can multiple ( 2 or more) groundbars be installed in Schneider Electric or Square D MB or MLO panels?

Issue:
How many ground bars can be installed on Schneider/Square D panelboards?

Product Line:
panels

Environment:
All

Cause:
Application

Resolution:
Multiple ground bars can be installed in panels, with no restrictions, other than the space to add them and making sure they do not hinder any wire bending spaces. All NEC codes must be followed which is the responsibility of the installer. Approval from the Local Authority having Jurisdiction may be required.