How can I avoid charging my batteries using the grid?

Issue:
Customer does not want to charge batteries with grid and/or Generator power.

Product Line:
Conext SW, XW series

Environment:
SW or XW system with Solar or other form of battery charging.

Cause:
Customer wants to charge only using solar or a different form of charging. (Not Grid or Generator)

Resolution:
Once you've set up your Charge Controller or charging system, make sure to 'Disable'  Charger. This can be done using your SCP or Combox. Select your inverter, in the Setup Menu you will find 'Charger' under 'Grid Support'.
NOTE: if you do not want to charge your batteries using Grid ONLY and you do want to charge using your Generator, you will have to 'Enable' Charging in your inverter.