Issue:
Can the TeSys T be changed from local to remote mode via the PLC? 

Product Line:
TeSys T Motor Management Controller

Environment:
Products sold in the North American Market

Cause:
Communications


Resolution:
No, this is not considered safe operation. 

The TeSys T can be changed from local to remote mode by changing input 6. If I.6 to C is high then the device is in remote control, if it is low then the device is in local control. 
The LTMCU handheld controller can also be set to modify the device from local to remote mode. 