How do you setup the PID sleep wake up function on the ATV630 process drive?

Issue:
How do you setup the PID sleep wake up function on the ATV630 process drive?

Product Line:
Altivar ATV630 and ATV930 drive

Environment:
All 

Cause:
setup sleep and wake up function.

Resolution:
Pump Functions main menu:

PID controller Menu

PID wake up and sleep function on the ATV630 Process drive. 

PID has to be activated and ON. 

Low speed has to be set to a value above 0 or 30hz as an example.

PID min output has to match your low speed or 30hz.

Pump Functions menu
Sleep/Wake up enter

Sleep setup example:
-Sleep detect mode = speed
-sleep min speed= 31 (needs to be 1hz higher than your low speed very important)
-Sleep delay= 3 seconds

Wake up Setup example:
-Wake up Menu (2nd Tab)
-Wake up mode= Error or Feedback.  Set to Error on this example
-Wake up Process Error= 3-5% will wake the drive back up. 

 