Video: How does the cover door latch and spring get installed in the QO and Homeline load center covers?

Issue:
Product repair parts

Product Line:
QO and Homeline Load Center covers

Environment:
Cover door latch and spring

Cause:
Installation

Resolution:
The video attached will show how to replace the latch and spring that is used on the doors for ALL the NEMA 1(Indoor) QO and Homeline load center covers.
The 
Door Latch and Spring kit is part #4020284450K
The attached video is ONLY to help with re-installation of the door latch and spring.
PLEASE make sure to read and follow all the below Safety Information BEFORE working on any electrical equipment.



Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment. 

1) Once all Safety steps are followed, begin the door latch and spring installation.
2) Make sure to remove the old spring and latch
3) insert the Spring from the FRONT side of the door, into the opening.
4) Place the plastic latch, from the front side, up against the spring and move the latch to the left with until it 'Pops' in place. 


NOTE: PLEASE MAKE SURE TO FOLLOW ALL SAFETY INSTRUCTIONS AND NEVER WORK ON ENERGIZED EQUIPMENT.