Technical FAQs

Ask a Question

Video: How to install aluminum or copper mechanical lug kit onto a Powerpact B-frame circuit breaker

Issue:
How do you install mechanical lug kits onto a B-frame breaker?
 
Product Line:
Molded Case Circuit Breakers
 
Environment:
Powerpact B-frame Circuit Breaker
 
Resolution:
 
Remove the green connection system cover (put a screwdriver or similar flat tool into slot in the connecter and push out) and the currently installed lug kit (put a screwdriver or similar flat tool into the gap between the lug kit and breaker on the back, and push the lug kit out). Then place the lug in front of the stab and bolt it to the stab with the provided screw. Once you have all 3 lugs installed, place the lug covers into place over the lugs and push down until they click into place. Then reinstall the green connection system cover and place the labels on the breaker. For further information, see the attached installation bulletin or see the video below:

Was this helpful?
What can we do to improve the information ?