Search FAQs
What overcurrent protection is required on the SDSA1175 or SDSA1175T Surge Protection device?
Issue:
What overcurrent protection to use on the SDSA1175 or SDSA1175T surge protection device?
Product Line:
Surge Protection Devices, SPD
Environment:
SDSA
Cause:
Breaker specification to protect equipment
Resolution:
The SDSA1175/SDSA1175T comes with #14 wire. You can connect it three different ways.
1) You can connect to a existing breaker feeding another load if lug terminals will accommodate multiple conductors.
2) You can connect to a dedicated 20A breaker.
3) You can direct bus connect because it is a Type 1 device. Type 1 SPD can be connected with or without an overcurrent protection device.
To reach a Surge Protection Specialist direct please call 800-577-7353 or email: spdtag@schneider-electric.com
What overcurrent protection to use on the SDSA1175 or SDSA1175T surge protection device?
Product Line:
Surge Protection Devices, SPD
Environment:
SDSA
Cause:
Breaker specification to protect equipment
Resolution:
The SDSA1175/SDSA1175T comes with #14 wire. You can connect it three different ways.
1) You can connect to a existing breaker feeding another load if lug terminals will accommodate multiple conductors.
2) You can connect to a dedicated 20A breaker.
3) You can direct bus connect because it is a Type 1 device. Type 1 SPD can be connected with or without an overcurrent protection device.
To reach a Surge Protection Specialist direct please call 800-577-7353 or email: spdtag@schneider-electric.com
Released for:Schneider Electric USA
Explore more
Explore more