What is the correct way to store a Motor Control Center before installation?

Issue:
What is the ambient temperature that you can install a Model 6 MCC in?

Product Line:
Motor control centers sold and supported in the USA.

Resolution:
If the MCC cannot be placed into service upon receipt, store it in a clean, dry, ventilated building free from temperature extremes.  Acceptable storage temperatures are from
0 degree C (32 degree F) to 40 degree C (104 degree F).  Acceptable humidity levels are 0 to 95%, non-condensing.

If the storage area is cool and/or damp, provide enough heat to prevent condensation inside the MCC.  
Note; failure to comply with these recommendations can void the warranty on the product.