Technical FAQs

Ask a Question

Cannot reset LXM32 drive to factory default

Issue:
Cannot reset LXM32 drive to factory default

Product Line:
LXM32, SoMove

Resolution:
If you remove a hardware component from the LXM32 configuration, you cannot do a factory reset unless you acknowledge this change.

In SoMove, you need to go to the "Start Up Messages" tab and acknowledge the removal of a hardware module (communication card, encoder card...).

After acknowledging the module removal, you should restart the drive and you should be able to do a factory reset.
Was this helpful?
What can we do to improve the information ?